Chilled Water Clamp LKS 13



Application
Suitable for secure prevention of condensation water at the pipe support location of refrigeration and cold-water pipelines. An optimal diffusion-tight connection with the pipe insulation is easily and safely achieved by fixing usual insulation materials to the clamp faces using adhesive. Recommended up to -0°C at normal ambient condition.
Scope of delivery
Consisting of pipe clamp and insulation insert. The one-piece insulation insert comprising two joined PUR elements forms a comprehensive connection between PUR element and pipe clamp all around the pipe.
The outer edges of the PUR elements are equipped with elastomer foam and coated by a black aluminium foil.
Type | Nominal thickness of the insulation [mm] | Size | Length of PUR element b [mm] |
---|---|---|---|
LKS 13 | 13 | 10 - 89 102 - 168 | 50 100 |
Technical Data
Size [mm] | Working load (tension) | Tightening torque [Nm] |
---|---|---|
13-10 - 13-12 | 0.3 kN | 2 |
13-15 - 13-16 | 0.4 kN | 2 |
13-18 - 13-26 | 0.5 kN | 2 |
13-28 - 13-48 | 0.6 kN | 2 |
13-50 - 13-57 | 1.0 kN | 2 |
13-60 - 13-64 | 1.1 kN | 2 |
13-70 | 1.2 kN | 2 |
13-76 - 13-80 | 1.3 kN | 2 |
13-89 | 1.4 kN | 2 |
13-102 | 1.6 kN | 2 |
13-108 - 13-114 | 1.7 kN | 2 |
13-125 | 1.9 kN | 2 |
13-133 | 2.0 kN | 2 |
13-139 | 3.3 kN | 2 |
13-160 | 3.7 kN | 2 |
13-168 | 3.8 kN | 2 |
The unsupported lengths as listed in DIN 1988 may be applied for types LKS 13 and LKS M 19 to 168.
The regulations of DIN 4140 have to be respected (an existing gap has to be sealed with sealant). Sealant DP 30/45 see Chapter "Fixed Point Packages".
Clamp material: | Steel, electro-galvanised |
Insulation insert: | Free of halogens |
PUR core: | Specific gravity 80 or 120 kg/m3 |
Thermal conductivity: | λ = 0.024 - 0.026 W/(mK) at 0°C λ = 0.038 W/(mK) at 10°C λ = 0.040 W/(mK) at 40°C |
Fire resistance: | EL (DIN EN 13501-1) |
Temperature range: | -40°C up to +105°C |
Insulation insert: | Up to 18 dB(A) |
Storage temperature: | ≥ 10°C |
* = Delivery time: 10 workdays