Slide Set GS H3G
Application
Heavy-duty Slide Set for plant construction. To be used preferably in combination with Sikla Pipe Clamp Stabil D-3G and Chilled Water Clamp SKS Top-2C.
Various connection options of the pipe clamps depending on the respective load: M12, M16 or with 1/2" adapters using the external thread (see Adapter AD f/f). Sound absorption by means of glass fibre reinforced polyamide slide rails.
Especially suitable for ceiling and floor mounting solutions and as a guide for rising pipes.
When using the version ULTRAglide the resultant shear force is halved. By this the realisation of optimized supporting structures is possible.
For wall mounting, we recommend the use of the Slide Set H3G on Sikla Support Bracket.
Installation
For pipes of NB 100 or larger having to be spaced at a distance from the Slide Set, or under conditions of reversed bending stress, the 3G triple thread nuts are to be secured by screwing on a 1/2" Locking Nut.
Technical Data
Permissible load for ceiling mounting: | 5.0 kN |
Permissible load for floor mounting: | 9.0 kN |
Permissible bending moment for wall mounting* for H3G2: | 350 Nm |
Temperature range (permanent exposure): | 130°C |
Version GS: | |
Static friction coefficient µ0 : | 0.18 |
Sliding friction coefficient µ: | 0.14 |
Version GS ULTRAglide: | |
Static friction coefficient µ0 : | 0.07 |
Sliding friction coefficient µ: | 0.07 |
Material: | |
Metal components: | Steel, electro-galvanised |
Slide bar: | Polyamide, glass fibre reinforced |
Version ULTRAglide: | With additional Nano coating |
* The permissible bending moment of the connecting element (threaded rod or threaded tube) may restrict the application!
Type | max. lever arm [mm] | max. lever arm ULTRAglide [mm] | max. slide path s [mm] |
---|---|---|---|
H3G | 250 | 400 | 100 |
H3G2 | 250 | 400 | 135 |
Adm. load FZ * under stress of fire
FWD 30 [N] | FWD 60 [N] | FWD 90 [N] | FWD 120 [N] |
---|---|---|---|
≤ 1.000 | ≤ 540 | ≤ 360 | ≤ 260 |
FZ = max. adm. tensile load
* The load capacity of the connecting elemente used is to be respected, this applies in particular under stress of fire.