Together we build.
siklaproof.

Application

For pipeline installations of fixed fire entinguishing systems, mainly used for Sprinkler systems.

Scope of delivery

Pipe Loop with rounded edges. Flange nuts and cup nuts are included in loose form.

Technical Data

Type
Nominal load
[kN]
26.9 - 60.3 2.0
76.1 - 114.3 3.5
133 - 168.3 5.0
219.1 8.5

Material:
Steel, galvanised as per DIN EN 10346

Approvals / Conformity

FM and VdS (No. G4850025) approved
The types from size 76,1 (2 1/2") onward have an FM- as well as an VdS-approval.

Pipe Loop N - G4850025 VdS PDF | 338.4 KB

TypeNBConnectionD
[mm]
H
[mm]
W
[kg]
Quantity
[pack]
Part
number
26.93/4"M8 (VdS)27650.05100 113336
33.71"M8 (VdS)34650.05100 102287
42.41 1/4"M8 (VdS)43650.05 50 102296
48.31 1/2"M8 (VdS)49700.06 50 102302
60.32"M8 (VdS)61790.06 50 102311
26.93/4"M10 (FM)27650.05100 113414
33.71"M10 (FM)34650.06100 102126
42.41 1/4"M10 (FM)43650.06 50 102135
48.31 1/2"M10 (FM)49700.06 50 102144
60.32"M10 (FM)61790.07 50 102153
         
76.12 1/2"M10 77 980.1425 102320
88.93"M10 901130.1625 102339
108M101101420.1925 102348
114.34"M101151420.1925 102357
133M121351550.2225 102366
139.75"M121421550.2225 102375
159M121611850.2525 102384
168.36"M121701850.2625 102393
219.18"M162212390.5610 102409