Chilled Water Clamp LKS 32
Application
Suitable for secure prevention of condensation water at the pipe support location of refrigeration and cold-water pipelines.
An optimal diffusion-tight connection with the pipe insulation is easily and safely achieved by fixing usual insulation materials to the clamp faces using adhesive. Recommended up to -0°C at normal ambient condition.
Scope of delivery
Consisting of pipe clamp and insulation insert. The one-piece insulation insert comprising two joined PUR elements forms a comprehensive connection between PUR element and pipe clamp all around the pipe.
The outer edges of the PUR elements are equipped with elastomer foam and coated by a black aluminium foil.
Type | Nominal thickness of the insulation [mm] | Size | Length of PUR-element b [mm] |
---|---|---|---|
LKS 32 | 32 | 15 - 70 76 - 273 | 50 100 |
Technical Data
Up to type LKS 32-168 the unsupported lengths as listed in DIN 1988 may be applied.
The regulations of DIN 4140 have to be respected (an existing gap has to be sealed with sealant). Sealant DP 30/45 see Chapter "Fixed Point Packages".
Clamp material: | Steel, electro-galvanised |
Insulation insert: | Free of halogens |
PUR-core: | Specific gravity 80 or 120 kg/m3 |
Thermal conductivity: | λ = 0.024 - 0.026 W/(mK) at 0°C λ = 0.038 W/(mK) at 10°C λ = 0.040 W/(mK) at 40°C |
Steam diffusion resistance factor: | µ ≥ 7000 |
Fire resistance: | EL (DIN EN 13501-1) |
Temperature range: | -40°C up to +105°C |
Insulation insert: | Up to 18 dB(A) |
Storage temperature: | ≥ 10°C |
Storage period: | 1 year |