Together we build.
siklaproof.
HDG & HCP Standard Range

Cantilever Bracket AK HCP

Application

Ready-to-use bracket for mounting pipes to walls or other building structures.

Installation

When used in combination with sliding elements, a tied rod is absolutely essential for absorbing the forces running along the centre line of the pipe.
For cantilever lengths > 500 mm we recommend the integration of a prop-up.

Technical Data

 



Anchor load classes
A = 1.5 kN
B = 2.5 kN
C = 3.5 kN
D = 6.0 kN

Restrictions
σzul ≤ 160 N/mm2
fperm ≤ L/150 for L > 450 mm
fperm ≤ 3 mm for L ≤ 450 mm
 

Material:
Steel, HCP
TypeL
[mm]
Wall plate
[mm]
b
[mm]
Dimensions of
elongated hole
[mm]
W
[kg]
Quantity
[pack]
Part
number
41/41 - 320320134 x 40 x 810013 x 180.9510 181667
41/41 - 570570134 x 40 x 810013 x 181.5010 181676
41/41 - 820820134 x 40 x 810013 x 182.001 161479
41/62 - 320320134 x 40 x 810013 x 181.4010 180119
41/62 - 570570134 x 40 x 810013 x 182.2510 180128
41/62 - 820820134 x 40 x 810013 x 183.051 180137
41/21 D - 320320134 x 40 x 810013 x 181.2510 180146
41/21 D - 570570134 x 40 x 810013 x 182.2510 180155
41/21 Dq - 320320134 x 40 x 810013 x 181.2010 180164
41/21 Dq - 570570134 x 40 x 810013 x 181.9510 190424