HDG & HCP Standard Range
Cantilever Bracket AK HCP
Application
Ready-to-use bracket for mounting pipes to walls or other building structures.
Installation
When used in combination with sliding elements, a tied rod is absolutely essential for absorbing the forces running along the centre line of the pipe.
For cantilever lengths > 500 mm we recommend the integration of a prop-up.
Technical Data
| |
Anchor load classes A = 1.5 kN B = 2.5 kN C = 3.5 kN D = 6.0 kN Restrictions σzul ≤ 160 N/mm2 fperm ≤ L/150 for L > 450 mm fperm ≤ 3 mm for L ≤ 450 mm |
Material: | Steel, HCP |